  Input Volts (On Load) Transformer 240V 1PH
 Output Transformer 110V 1PH (55.0.55) CTE
 Ingress Protection BS EN60529 IP00
 Frequency – Hz. 50/60
 Type Dry
 Ambient Temperature Degrees C 25°
 Duty Cycle Continuous
 Earth Screen Included
 Dielectric Class 3kV
 Item Data Option A
 Rating 2kVA (continuous)
 Enclosed Steel Enclosure Floor mount Tower unit (Marine Blue RAL5002) Special IP67
 Height (mm) Approx. H 900
 Length (mm) Approx. L 305
 Depth (mm) Approx. W 230
Weight (kg) Approx. 32.14
   Part B – Fittings
Input Device Hard Wire, Cable Entry via Base 2 x 35mm 4C Armoured (Client To Fit) Provision to Accept
 Isolation Switch 1 x 63A 4P Mains Isolation Switch
  Output 1 (Non Isolated) 1 x 32A 400V 5P IP67 Socket
 Outlet 1 Protection 1 x 32A TP Type “C” MCB & 1 x 40A 30MA 4P RCD for 32A 400V S/O
 Transformer Input Protection 1 x 16A DP Type “D” MCB
 Output (Isolated) 1 x 16A 110V 2P+E IP67 Socket
 Output Protection 1 x 16A DP Type “C” MCB & 1 x 25A DP 30mA RCD for 16A 110V S/O
  Fittings All MCB &, RCD under IP65 quick release Covers
 Standard BS EN 61558
 All our quality standards and procedures are monitored independently to BS EN 9001, and are subject to regular external and internal audits.